• <table id="cgceg"></table>
  • Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
    CN EN

    Vacuum interrupter for outdoor circuit breaker TD424B

    Model:VITD24/1250-20

    Category:VI for outdoor circuit breakers

    Product details

    1.jpg
    Main Technical Specification
    VOLTAGE RATINGS
    Rated voltage(Ur)kV24
    Rated short-time(1min)power-frequency withstand voltage(Ud)kV79
    Rated lightning impulse withstand voltage(Peak)(Up)kV145
    Rated frequency(fr)Hz50
    CURRENT RATINGS
    Rated current(Ir)A1250
    Circuit resistance at lowest rated contact forceμΩ≤30
    Rated short-circuit breaking current(lsc)kA20
    Breaking operations of rated short circuit breaking currentTimes30
    Rated short-time withstand current(lk)kA20
    Rated duration of short-circuit(tk)s4
    Rated peak withstand current(lp)kA50
    Rated short-circuit making current(lMc)kA50
    Rated cable-charging breaking current(lc)A25
    Rated breaking current of single capacitor bank(lsb)A400
    Rated breaking current of back-to-back capacitor bank(lbb)A400
    MECHANICAL DATA
    Weight of movable partskg≤1.5
    Closing force due to bellow and atmosphereN120±50
    Force required to hold contacts open at full strokeN190±60
    MECHANICAL REQUIREMENTS
    Clearance between open contactsmm12±1
    Average opening speed (contact close position~75%contact gap)m/s1.5±0.2
    Average closing speed (30%contact gap-contact close position)m/s0.8±0.2
    Rated added external contact final forceN2000±200
    Added external contact force at contact touch point1400±150
    Contact bouncing duration at closing operationms≤2
    Closing and opening non-simultaneity of three-phase contactsms≤1
    Maximum rebound during openingmm≤2
    LIFE
    Storage lifeyears20
    Rated mechanical enduranceTimes10000
    Contacts limit erosionmm3